The DSE 6020 MKII is an Auto Mains (Utility) Failure Control Module developed to provide a wide range of operating and monitoring features for single diesel and gas gen-sets.
OVERALL SIZE
216 mm x 158 mm x 43 mm (8.5” x 6.2” x 1.5”)
PANEL CUTOUT SIZE
184 mm x 137 mm (7.2? x 5.3?)
MAXIMUM PANEL THICKNESS
8.0 mm (0.3”)
WEIGHT
0.48kg
PRODUCT VARIANTS
6020-03 – MKII Auto Mains (Utility) Failure Control Module
6020-04 – MKII Auto Mains (Utility) Failure Control Module (Htr)
DC SUPPLY
CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained
during cranking.
MAXIMUM OPERATING CURRENT
100 mA at 12 V, 105 mA at 24 V
MAXIMUM STANDBY CURRENT
60 mA at 12 V, 55 mA at 24 V
MAXIMUM SLEEP CURRENT
40 mA at 12 V, 35 mA at 24 V
GENERATOR?&?MAINS?(UTILITY)
VOLTAGE?RANGE
15 V to 415 V AC (Ph to N)
26 V to 719 V AC (Ph to Ph)
FREQUENCY?RANGE
3.5 Hz to 75 Hz
INPUTS
DIGITAL INPUTS A to F
Negative switching
ANALOGUE INPUTS A to C
Configurable as:
Negative switching digital input
0 ? to 480 ?
ANALOGUE INPUT D
Configurable as:
Negative switching digital input
0 V to 10 V
4 mA to 20 mA
0 ? to 480 ?
OUTPUTS
OUTPUT A (FUEL)
10 A short term, 5 A?continuous,
at supply voltage
OUTPUT B (START)
10 A short term, 5 A?continuous,
at supply voltage
AUXILIARY OUTPUTS C, D, E &?F
2 A DC at supply voltage